Wet chemical fire-extinguishing systems shall comply. Additional notes required for solid fuel burning.
Place the following notes verbatim on the plan.
Where a building fire alarm or monitoring system is installed, the automatic fire-extinguishing system(s) shall be monitored in accordance with NFPA 72. CFC 904.3.5 Monitoring of commercial cooking hood and duct systems will be field verified only and installation must be performed by a contractor with a valid C-10 License. A separate fire alarm plan is not required.
The approved set of plans shall be delivered by the contractor to the owner/manager to be kept on-site for reference and inspection records along with the completed “Wet Chemical Acceptance Test Report”.
The system shall be pre-tested prior to CCFD inspection to determine that the system is properly installed and functions in accordance with the approved plans and the manufacturer’s installation and maintenance manual. The complete technical manual shall be made available to the inspector. Please note, if a full manual is not available, the inspection may be discontinued and a rescheduling fee will apply. Testing during the CCFD inspection shall include a manual and automatic activation via fusible link. A shut down of all electrical and gas cooking equipment shall also be demonstrated. Nozzle type, height, and orientation relative to placement of cooking appliances will also be verified during the inspection.
The entire duct system shall be inspected at a minimum per Table 609.3.3.1. If during the inspection it is found that the hood, grease removal devices, fans, ducts or other appurtenances have an accumulation of grease, such components shall be cleaned. CFC 609.3.3.2
Solid cooking appliances shall be inspected, cleaned, and maintained in accordance with the following per 2008 NFPA 96:
Site-Built Solid Fuel Cooking Appliances